The SYB5-80 DC miniature circuit breaker, supplied by China-based manufacturer Zhejiang Soutya New Energy LLC, provides protection for AC 230/400V and DC 300~1200V circuits. Key Features
▶ Common for AC and DC (AC230/400V、 DC300~1200V)
▶ No positive or negative polarity distinction, bidirectional protection, easier to installation.
▶ High breaking short arc, higher safety.
The SYB5-80 DC miniature circuit breaker, supplied by China-based
manufacturer Zhejiang Soutya New Energy LLC, is a 300–1200 V DC and 230/400
V AC bidirectional and non-polarized miniature breaker, with a 10 KA AC /
6KA DC breaking capacity, designed for high-voltage protection in PV
systems, battery energy storage systems (BESS), and electric vehicle
charging equipment.
Characteristic
Short Circuit Protection, Overload Protection
Ultimate breaking capacity:10 KA AC / 6KA DC
Non-polar,bidirectional protection
Short arcing
Flame Retardant Material
Application scenarios
1.Residential & commercial PV combiner boxes
Protects 300–1200 V DC string inputs and 230 V/400 V AC inverter outputs;
single-pole width doubles density in small enclosures.
2.PV-battery hybrid inverters
Bidirectional, non-polarized breaker on 300–1200 V DC battery bus handles
charge and discharge currents without rewiring.
3.Small DC EV chargers (≤ 20 kW)
600–1200 V DC output bus protection; 6 kA breaking clears arc faults during
plug-in/out events.
4.Telecom & data-center DC racks
Pole combinations safeguard 48 V/240 V/380 V server or UPS branches up to
1200 V DC; DIN-rail mount saves cabinet space.
5.Low-voltage DC micro-grids
380–1200 V DC distribution for LED lighting, fans or pumps; B/C/D curves
match diverse load characteristics.
6.Harsh or high-altitude sites
−30 °C to +70 °C, no derating up to 2 000 m, fits IP66 enclosures for
carports, agrivoltaic and rooftop plants.
Technical Parameter
Model
SGB5-80
Pole
1P
2P
3P
4P
Rated Working Voltage Ue
230VAC
400VAC
400VAC
400VAC
300VDC
600VDC
900VDC
120VDC
Maximum frame current
80A
Rated Current In
6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A
Rated Insulation Voltage Ui
690VAC
600V DC 900VDC 1200VDC
Rated impulse withstand voltage Uimp
8kV
Tripping characteristics
B/C/D
Tripping type
Thermal-magnetic
Ics Operational breaking capacity lcs
7.5kA(AC)6kA(DC)
Icu Ultimate breaking capacity lcu
10kA(AC)6kA(DC)
Electrical Life
Actual Average Value
Average 4000 times(AC)1000 times(DC)
Standard Specified Value
1500 times(AC)300 times(DC)
Mechanical Life
Actual Average Value
≥15000 Times
Standard Specified Value
8500 times(AC) 9700 times(DC)
Overvoltage category
Ⅲ
Pollution degree
3
Protection Level
IP40;Termina IP20
Moisture and heat resistance
Category 2
Relative Humidity
≤95%
Vibration Resistance
Basis IEC60068-2-6
Mechanical impact resistance parameters
Basis IEC60068-2-27
Wiring Capacity
25~35mm²
Wiring Torque
3.0Nm
Operating Ambient Temperature
-30℃~+70℃
Storage Ambient Temperature
-40℃~+85℃
Installation Method
DIN35
Altitude
≤2000m
Weight
0.13kg/Pole
Dimension
Length
85mm
Width
18mm
36mm
54mm
72mm
Height
Max78mm
Package
Pcs/Box
12
6
4
3
Box/Carton
10
Carton/Pallet
80
Storage
The product should be stored in a well-ventilated warehouse, with
relative humidity not exceeding 80%, and the ambient temperature
should be between -40℃ and+80℃.Additionally, there should be no
acidic, alkaline, or corrosive gases present.
DC Wiring Diagram
Appearance and Installation Dimensions
Derating Factor
Temperature Derating Factor Table
Temperature
-30℃
-25℃
-20℃
-15℃
-10℃
-5℃
0℃
5℃
10℃
15℃
Rated Operating Current Coefficient
1.279
1.261
0.242
1.223
0.204
1.182
1.161
1.143
1.127
1.103
Temperature
20℃
25℃
30℃
40℃
45℃
50℃
55°C
60℃
65°C
70℃
Rated Operating Current Coefficient
1.079
1.063
1.047
1
0.984
0.968
0.952
0.922
0.904
0.891
Altitude Derating Factor Table
Altitude /m
2000
3000
4000
5000
Rated working Current Coefficient
1
0.96
0.91
0.86
Rated working Voltage Coefficient
1
1
1
1
Rated Power Frequency Withstand Voltage Coefficient
1
0.9
0.82
0.71
Rated Impulse Withstand Voltage Coefficient
1
0.9
0.82
0.71
Rated Limit Short-circuit Segment Capacity and Electrical Life
Coefficient
1
0.82
0.7
0.6
Derating factor table for side-by-side installation of MCBS
No.of MCB
1
2~3
4~5
6~8
9~10
In≤25A Coefficient
1
0.96
0.9
0.8
0.7
32A≤In≤63A Coefficient
1
0.92
0.8
0.7
0.6
80A≤In≤125A Coefficient
1
0.9
0.8
0.7
/
Accessory
MX auxiliary release device
Rated Control Voltage Us
DC:24~48V AC:110~230V
Maximum Tripping Time
<10ms
Coil Resistance
50
Limit current
≥1.6A
Mechanical Life
10000times
Electrical Life
4000times
Wiring torque
0.8N ·m
Wiring capability
1.0mm²Hard wire
1.0mm²Soft wire with terminal lugs
Operating Temperature Range
-30℃~+70℃
Environmental conditions
There should be no explosive hazardous substances, and no harmful
gases or conductive dust that can corrode or damage insulation
Assembly position
To the left side of the circuit breaker
Installation conditions
DIN35mm standard rail mounting
Auxiliary contact OF
Contact breaking capacity
AC13:le=3A;Ue=250V
AC15:le=2A;Ue=250V
DC12:le=0.5A;Ue=110V
Minimum Operating Voltage
5V
Minimum Operating Current
10mA
Rated Insulation Voltage
500V
Rated limited short-circuit current
1000A
Agreed heating current Ith
4A
Mechanical Life
10000(times)
Electrical Life
4000(times)
Wiring torque
0.8N ·m
Wiring capability
1.0mm²
Number of contacts
1 normally open, 1 normally closed
Operating Temperature Range
-30℃~+70℃
Environmental conditions
There should be no explosive hazardous substances, and no harmful
gases or conductive dust that can corrode or damage insulation
East of No.148, Wei 12th Road, Economic Development
Zone,Yanpan Subdistrict,Yueqing City,Wenzhou,Zhejiang
Province,China
For inquiries about DC Combiner Box, Charging Pile, Circuit Breaker or price list, please leave your email to us and we will be in touch within 24 hours.
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.
Privacy Policy