Products
AC 230V Surge Protective Device
  • AC 230V Surge Protective DeviceAC 230V Surge Protective Device

AC 230V Surge Protective Device

The GNS1 AC 230V Surge Protective Device , supplied by China manufacturer Zhejiang Soutya New Energy LLC,applied in energy storage, charging piles, PV AC combiner boxes, and grid connected boxes.

The GNS1 AC 230V Surge Protective Device , supplied by China manufacturer Zhejiang Soutya New Energy LLC, delivers 275 V AC (Uc) protection for single-phase 230 V networks with 20 kA nominal and 40 kA maximum discharge-current capability, providing Class II surge protection for residential and light-commercial distribution boards.

Technical Parameter

NominalVoltage
(Uc)
Pole NominalDischargeCurrent
(In)(8/20μs)
Executivestandards
AC 230V 1P、2P 20KA~40KA GB/T 18802.11
IEC/EN 61643-11
model GNS1-D/-140-5(10) GNS1-D/-275-5(10) GNS1-D/-320-5(10) GNS1-D/-385-5(10) GNS1-D/-420-5(10)
Max continuous operation voltage Uc-(V) 140 275 320 385 420
Voltage protection level UP(KV) ≤1.0 ≤1.0 ≤1.5 ≤2.0 ≤2.0
Nominal discharging current In(8/20μs) (KA) 5
Max discharging current Imax(8/20μs) (KA) 10
Response time (ns) <25
Width (mm) 18
Color yellow
Protection degree IP20
Shell material Strong flame-retardant PBT
Fuse or circuit breaker (A) 10–16
connection specification zero line 25–35mm²
Earth line 4.0–35mm²
Signal line 1.5mm²
model GNS1-C/-550-20 GNS1-C/-320-30 GNS1-C/-385-30 GNS1-C/-385-40 GNS1-C/420-40
Nominal discharging current In(8/20μs) (KA) 5 5 5 5 5
Max continuous operation voltage UC~(V) 550 320 385 385 420
Voltage protection level UP(KV) 2.5 1.5 2 2 2
Nominal discharging current In(8/20μs) (KA) 20 30 30 40 40
Max discharging current Imax (8/20μs)KA 40 60 60 80 80
Response time ns <25
Width mm 18
color yellow
Protection degree IP20
Shell material Strong flame-retardant PBT
Fuse or circuit breaker(A) 10-16
connection specification zero line 2.5-35mm²
Earth line 4.0-35mm²
Signal line 1.5mm²

Installation location and usage

GNS1-C

C degree thunder current SPD protection, used as the iso-electric level connection when there is a thunder attack;install the surge protector at the cross between LPZOB and LPZ1 or LPZ2;Normally the protector is installed in the power distribution box of building power distribution cabinet,computer center, telecom equipment room, elevator control room, wiring TV equipment room, building self-control room, safe monitoring center, fire control center, industry self-control room, frequency inverter control room, hospital surgery room, ICU room and the place where electronic medical equipment; And it is also can be installed in the residual lighting power distribution box below 6 floor ,for villa ,the SPD should be installed in the resident power distribution box.

GNS1-D

The SPD is installed at the cross between LPZand LP23 or between LPZ2 and LPZ3.It is suitable to the residual power distribution box ,computer equipment, telecom equipment, electronic equipment or the socket box at front of control equipment or near the equipment.

Components introduction

Invalid tripping device

There is invalid tripping device on the protector modular. When the protector is invalid cause of over thermal, breakdown, the invalid tripping device can separate from the power grid automatically and the indication signal is sent out. When the protector is normal, the green is displayed. When invalid tripping, red is displayed.

Alarming apparatus

The alarming apparatus is power supplied by 220 V AC. The indication lamp is green when the protector work normally, normal open contact is closed and the normal closed contact is open. Audio light alarming function: when the protection modular is invalid, the alarm will be beeping, the normal green lamp will be changed into red lamp at the same time. When the maintainer press the stop button, the buzz will stop, but the red lamp still is on. If the fault is not solved within 24 hours, the alarming apparatus will send out beep once again.

Remote signal contact

The protector can be with remote signal contact. The contact is normal open. If one or more modular of protector is invalid, the contact will be closed and send out fault signal. The rated parameter of remote signal contact is AC 36V, 1A.

Zhejiang Soutya New Energy LLCZhejiang Soutya New Energy LLC

Hot Tags: AC 230V Surge Protective Device
Send Inquiry
Contact Info
  • Address

    East of No.148, Wei 12th Road, Economic Development Zone,Yanpan Subdistrict,Yueqing City,Wenzhou,Zhejiang Province,China

For inquiries about DC Combiner Box, Charging Pile, Circuit Breaker or price list, please leave your email to us and we will be in touch within 24 hours.
X
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
Reject Accept