The GNS1 AC 400V Surge Protective Device , supplied by China manufacturer Zhejiang Soutya New Energy LLC,applied in energy storage, charging piles, PV AC combiner boxes, and grid connected boxes.
The GNS1-C/420-40 AC 400V Surge Protective Device, supplied by China-based
manufacturer Zhejiang Soutya New Energy LLC, delivers 420 V AC (Uc)
protection for three-phase 400 V networks with 40 kA nominal and 80 kA
maximum discharge-current capability, providing Class II surge protection
for industrial distribution boards and switchgear.
Technical Parameter
NominalVoltage
(Uc)
Pole
NominalDischargeCurrent
(In)(8/20μs)
Executivestandards
AC 400V
3P、4P
40KA~80KA
GB/T 18802.11
IEC/EN 61643-11
model
GNS1-D/-140-5(10)
GNS1-D/-275-5(10)
GNS1-D/-320-5(10)
GNS1-D/-385-5(10)
GNS1-D/-420-5(10)
Max continuous operation voltage Uc-(V)
140
275
320
385
420
Voltage protection level UP(KV)
≤1.0
≤1.0
≤1.5
≤2.0
≤2.0
Nominal discharging current In(8/20μs) (KA)
5
Max discharging current Imax(8/20μs) (KA)
10
Response time (ns)
<25
Width (mm)
18
Color
yellow
Protection degree
IP20
Shell material
Strong flame-retardant PBT
Fuse or circuit breaker (A)
10–16
connection specification
zero line
25–35mm²
Earth line
4.0–35mm²
Signal line
1.5mm²
model
GNS1-C/-550-20
GNS1-C/-320-30
GNS1-C/-385-30
GNS1-C/-385-40
GNS1-C/420-40
Nominal discharging current In(8/20μs) (KA)
5
5
5
5
5
Max continuous operation voltage UC~(V)
550
320
385
385
420
Voltage protection level UP(KV)
2.5
1.5
2
2
2
Nominal discharging current In(8/20μs) (KA)
20
30
30
40
40
Max discharging current Imax (8/20μs)KA
40
60
60
80
80
Response time ns
<25
Width mm
18
color
yellow
Protection degree
IP20
Shell material
Strong flame-retardant PBT
Fuse or circuit breaker(A)
10-16
connection specification
zero line
2.5-35mm²
Earth line
4.0-35mm²
Signal line
1.5mm²
Application scenarios
1.Main LV switchgear 400 V, 50 Hz three-phase TN-S/TN-C-S systems: installed
after the main breaker as Class II surge-protection node, diverting
lightning or switching overvoltages.
2.Industrial motor-distribution boards Incoming side of VFD, servo and MCC
panels; suppresses switching surges and induced lightning, safeguarding
expensive power semiconductors.
3.Data-center rack PDUs 400 V dual-bus or triple-bus architecture;
hot-swappable module permits on-line replacement, keeping servers, UPS and
battery banks running.
4.Commercial building floor substations Feeder circuits downstream of
transformers; reduces equipment trips and insulation breakdown caused by
external surges or ground-potential rise.
5.Renewable-energy enclosures 380 V PV AC combiner boxes and PCS AC
terminals; works with DC SPDs to provide complete AC/DC surge immunity.
6.Rail & tunnel power distribution 400 V traction ring-main cabinets and
platform lighting boards; withstands strong EMI and guarantees reliable
signalling and communication power.
7.Shore-to-ship supply & EV-charging parks 400 V bus feeding high-power
chargers; mitigates paralleling surges, extends charger-module life and cuts
maintenance downtime.
Installation location and usage
GNS1-C
C degree thunder current SPD protection, used as the iso-electric level
connection when there is a thunder attack;install the surge protector at the
cross between LPZOB and LPZ1 or LPZ2;Normally the protector is installed in
the power distribution box of building power distribution cabinet,computer
center, telecom equipment room, elevator control room, wiring TV equipment
room, building self-control room, safe monitoring center, fire control
center, industry self-control room, frequency inverter control room,
hospital surgery room, ICU room and the place where electronic medical
equipment; And it is also can be installed in the residual lighting power
distribution box below 6 floor ,for villa ,the SPD should be installed in
the resident power distribution box.
GNS1-D
The SPD is installed at the cross between LPZand LP23 or between LPZ2 and
LPZ3.It is suitable to the residual power distribution box ,computer
equipment, telecom equipment, electronic equipment or the socket box at
front of control equipment or near the equipment.
Components introduction
Invalid tripping device
There is invalid tripping device on the protector modular. When the
protector is invalid cause of over thermal, breakdown, the invalid tripping
device can separate from the power grid automatically and the indication
signal is sent out. When the protector is normal, the green is displayed.
When invalid tripping, red is displayed.
Alarming apparatus
The alarming apparatus is power supplied by 220 V AC. The indication lamp is
green when the protector work normally, normal open contact is closed and
the normal closed contact is open. Audio light alarming function: when the
protection modular is invalid, the alarm will be beeping, the normal green
lamp will be changed into red lamp at the same time. When the maintainer
press the stop button, the buzz will stop, but the red lamp still is on. If
the fault is not solved within 24 hours, the alarming apparatus will send
out beep once again.
Remote signal contact
The protector can be with remote signal contact. The contact is normal open.
If one or more modular of protector is invalid, the contact will be closed
and send out fault signal. The rated parameter of remote signal contact is
AC 36V, 1A.